Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> Moulded Case Circuit Breaker >> SM1L Series Earth Leakage Circuit Breaker
     
   
 
1. Application
 
SM1L series earth leakage circuit breaker are one of the new type earth leakage breakers which have been developed by the company using international advanced design and manufacturing technology. Suitable for a line of AC50Hz/60Hz, rated voltage up to 400V, rated current 16A to 630A. and is acted as infrequent changeover of circuit or infrequent starting of motor. The breaker has overload, short-circuit and under-voltage protective function, which can protect the circuit and the power equipment against damage, meanwhile, it can provide protection to these fire dangers that caused by these long-time existed grounding fault that can not be detected by the over-current protection.
This breaker can be installed vertically(upright) or horizontally(transverse).
Wiring of the breaker can not be in adverse direction, that means power supply line must be connected to terminal 1,3 and 5,and the load line connected to terminal 2,4 and 6.
The rated residual operating current I△n and the maximum breaking time can be adjusted on site according to practical condition.
The leakage protection module still can work normally when the phase voltage reduce to 50V. It has the same overall size with the AM1 series breakers, which make the installation more exchangeable.
The breakers are suitable for isolation, its symbol are:
The breakers comply with the demands of the following standards:
IEC60947-1 and GB/T 14048.1 General
IEC60947-2 and GB 14048.2 Low voltage breakers
IEC60947-4 and GB 14048.4 Contactors and motor starters
IEC60947-5.1 and GB 14048.5 Electrical equipments of electromechanical control circuit

 
 
2. Main Technical Specifications
 
Type SM1L-100 SM1L-225 SM1L-400 SM1L-630
Frame Current Inm(A) 100 225 400 630
Rated current In(A) (10)16,20,25,32,40,50,63,80,100 100,125,160,180,200,225 225,250,315,350,400 400,500,630
Pole Number 3 4 3 4 3 4 3 4
Rated Insulation Voltage Ui(V) AC800
Rated Working voltage Ue(V) AC 400V
Rated impulse with stand voltage Uimp(V) 8000
Arc-over Distance(mm) >50
Breaking capacity grade M H M H M M
Limiting short-circuit breaking capacity lcu (kA) AC400V 50 85 50 50 85 50 65 65
Service short-circuit breaking capacity lcs(kA) AC400V 35 50 35 35 50 35 42 42
Rated residual operating current I △ n(mA) Non-delay type 100/300/500
Delay type 100/300/500 300/500/1000
Rated residual nonoperatingcurrent I △no(mA) 1/2 I △ n
Operation performance (time) Electrified 1500 1000 1000 1000
Unelectrified 8500 7000 4000 4000
 
Note: According to the pole number of product, it calssifies three and four poles. The neutral pole (N-Pole) of the four-poles products has four types:
Type A: N-pole without over-current release unit, it has been connected all the time, not closing and opening with the other three poles.
Type B: N-pole without over-current release unit, which closing and opening with the other three poles.
Type C: N-pole fixed with over-current release unit, which closing and opening with the other three poles.
Type D: N-pole fixed with over-current release unit, it has been connected all the time, not closing and opening with the other three poles.
1. The limiting breaking and arc-over distance includes horizontal and vertical installation.
2. If the three-pole breaker of this series is connected with three phase load, the load can not have neutral line, otherwise the breaker will have fault action.
3. If the three-pole breaker of this series is connected with single phase load, the phase line willbe connected to the left pole, and the neutral line is connected to the right pole, the middle pole is blanket
 
 
3. Protection Characteristic
 
The thermal release of the breaker has again-time-limit property; the electromagnetic release is inst. Operation, its property see table 2(for distribution),table 3 (motor protection).
 
Rated current of Release(A) Thermal release (ambient temperature+40OC) Electromagnetic release operating current(A)
1.05In(cold state ) non-operating time (h) 1.03In(hot state) acting time (h)
10 ≤ In ≤ 63 1 1 10In±20%
63 ≤ In ≤ 125 2 2
125 ≤ In ≤ 630 2 2 5In±20% 10In±20%
 
Rated current of Release Thermal release (ambient temperature +40OC) Electromagnetic Release operating current(A)
1.0In (cold state) non-operating time(h) 1.20In(hot state) acting time(h) 1.50In(thermal state) operating time 7.2In(cold state) operating time
10≤In≤400 2 2 8min 6s < TP ≤ 20S 12In±20%
 
 
4. Residual current operating time of earth leakage circuit breaker
 
4.1 Non-delay type operation characteristics see table 4(I△n≤30mA should be Non- delay type)
 
Rated current I△n 2I△n 5I△na 10I△n
Non-delay type Max.breaking time(s) 0.3 0.15 0.04 0.04
 
Note: ato I△n≤30mA earth leakage circuit breaker, 0.25A can instead of 5I△n According toa, adopt 0.25A, then 10 I△n is 0.5A.
 
4.2 Delay type operation characteristics see table 5
 
Limiting non-driven time of delay type earth leakage circuit breaker according to 2l△n,operation characteristics see table 5
 
Delay time (s) Max. breaking time(s) at I△n Limiting non-driven time (s) at 2 I△n Max. breaking time(s) Max. breaking time(s) at 5I△n Max. breaking time(s) at 10 I△n
0.1 0.4 0.06 0.2 0.15 0.15
0.2 0.5 0.06 0.2 0.15 0.15
0.3 0.6 0.1 0.4 0.3 -
0.4 0.7 0.2 0.5 0.4 -
0.5 0.8 0.3 0.6 0.5 -
0.6 0.9 0.4 0.7 0.6 -
0.7 1.0 0.5 0.8 0.7 -

 
5 .Accessories of circuit breaker
5.1 The external accessories of the breaker
 
Motor-driven operation device
1) Wiring diagram of type CDM electromagnetic operation device(fitting AM1L-100,225) see thefollowing drawing (wiring diagram of the external accessories of the breaker in the dotted frame)
 
2) Wiring diagram of type CD motor-driven operation device (fitting AM1L-400I630) see belows(wiring diagram of the external accessories of the breaker in the dotted frame)
 
Code description: SB1 SB2 stand for push button.(provided by users themselves) Number "1" "2" "3" stand for number of wiring terminals.Voltage rating: AC50Hz 230V 400V, DC 220V
 
Rotary handle operation device The mechanism is used in moulded case circuit breaker to operate the draw-out panel. Powerdistribution panel and supply box outside the panel by turning the handle,and to ensure thedoor of panel would not be openned when the breaker being on. The hand-drive mechanism can be equiped with two types of operation one is "A" modelsquare handle , the other is "B" model round handle.
 
5.2 The internal accessories of the breaker
 
5.2.1 Release pattern and accessories code see following table
 
 
Release patternand accessories code Name\Type SM1L- 100,225 SM1L-400 SM1L-630
200, 300 No accessories 200: Magnetic release (only short circuit protection)
300: Thermal magnetic release(both overload and short circuit protection)
208, 308 Alarm contact
210, 310 Shunt release
220, 320 Auxiliary contact
230, 330 Under-voltage release
228, 328 Auxiliary contact,Alarm contact
 
5.2.2 The technical parameter and functions of the accessories
 
Accessory Rated operating voltage (V)
AC50Hz DC
Shunt Release Us 220(230) 380(400) 110 220
Under-voltage Release Us 220(230) 380(400)

Auxiliary contact and Alarm contact: Auxiliary contact is as some as Alarm contact , the techni-cal parameter see following table
 
Rated heating current Ith (A) Rated operating current Ie(A) Suited Frame Inm(A)
AC380V DC220V
3 0.3 0.15 100, 225
3 0.4 0.15 400, 630
 
Accessories name Function Wiring connection diagram
Alarm contact
Indicate circuit breaker at tripping
Auxiliary contact
Indicate circuit breaker at opening or closing
Shunt release
The shunt release should make the breaker trip reliably when theoperatiopn voltage is 70%-110% of rated control voltage
Under-voltage
When Ue is 35%-70% of the rated control voltage, the under voltagerelease should make the breaker trip correctlyWhen Ue is 85%-110% of the rated control voltage, the under voltagerelease should make the breaker closeIn case of Ue less than 35%of the rated control voltage should preventthe breaker from closing
 
Type Outline dimensions Installation dimensions
Back panel connection Back panel connection Plug-in
W L H W1 L1 L2 H1 H2 L3 H3 D L4 L5 H4 H5 H6 C D D1 A B d
SM1L-100M,H/3P 92 150 92 60 200 200 132 110 28.5 90 93 168 92 50 64 76 60 56 6.5 30 129 4.5
SM1L-100M,H/4P 122 150 92 90 200 200 132 104 28.5 90 93 168 92 50 64 76 60 56 6.5 30 129 4.5
SM1L-225M,H/3P 107 165 90 70 265 265 144 110 24 93 100 183 94 50 71.5 86.5 90 54 6.5 35 126 5.5
SM1L-225M,H/4P 142 165 103 105 265 265 144 127 24 93 100 183 94 50 710.5 86.5 70 54 6.5 35 126 5.5
SM1L-400M,H/3P 150 257 106.5 96 441 441 224 146.5 38 164 108.5 279 - 60 83.5 106.5 105 129 8.5 44 194 7
SM1L-400M,H/4P 198 257 106.5 144 441 441 224 146.5 38 164 108.5 279 - 60 83.5 106.5 70 129 8.5 44 194 7
SM1L-630M,H/3P 210 280 115.5 145 480 480 243 155 45.3 158 84 296 - 61 97 148 140 143 10 70 243 7
SM1L-630M,H/4P 280 280 115.5 210 480 480 243 155 45.5 158 84 296 - 61 97 148 210 143 10 70 243 7

 

 

  Back

Copyright ©. Sunfad Electrical Group Co., Ltd. All Rights Reserved